When sizing a generator set based on kVA output, understanding the corresponding amperage is crucial for proper load management and system design. As an example, at 400 V (line-to-line) and 50 Hz, a 100 kVA generator can supply roughly 144 A per phase, while a 500 kVA unit can provide about 722 A per phase under similar conditions. These values will differ slightly based on system voltage, frequency, and power factor, making precise calculations and verification essential to ensure reliable and efficient generator operation.
SIZING TABLE – KW, VOLTAGE, AMPERAGE
3 PHASE AMPERES – 80% POWER FACTOR*
kW Times 1000 divided by (Volts*1.73) *.80
kVA |
kW |
120 |
208 |
220 |
240 |
277 |
480 |
5 |
4 |
24.1 |
13.9 |
13.1 |
12.0 |
10.4 |
6.0 |
6 |
5 |
30.1 |
17.4 |
16.4 |
15.1 |
13.0 |
7.5 |
9 |
7 |
42.1 |
24.3 |
23.0 |
21.1 |
18.3 |
10.5 |
11 |
9 |
54.2 |
31.3 |
29.6 |
27.1 |
23.5 |
13.5 |
13 |
10 |
60.2 |
34.7 |
32.8 |
30.1 |
26.1 |
15.1 |
15 |
12 |
72.3 |
41.7 |
39.4 |
36.1 |
31.3 |
18.1 |
19 |
15 |
90.3 |
52.1 |
49.3 |
45.2 |
39.1 |
22.6 |
25 |
20 |
120.4 |
69.5 |
65.7 |
60.2 |
52.2 |
30.1 |
31 |
25 |
150.5 |
86.8 |
82.1 |
75.3 |
65.2 |
37.6 |
34 |
27 |
162.6 |
93.8 |
88.7 |
81.3 |
70.4 |
40.6 |
38 |
30 |
180.6 |
104.2 |
98.5 |
90.3 |
78.3 |
45.2 |
44 |
35 |
210.7 |
121.6 |
115.0 |
105.4 |
91.3 |
52.7 |
45 |
36 |
216.8 |
125.1 |
118.2 |
108.4 |
93.9 |
54.2 |
50 |
40 |
240.8 |
139.0 |
131.4 |
120.4 |
104.3 |
60.2 |
56 |
45 |
271.0 |
156.3 |
147.8 |
135.5 |
117.4 |
67.7 |
63 |
50 |
301.1 |
173.7 |
164.2 |
150.5 |
130.4 |
75.3 |
69 |
55 |
331.2 |
191.1 |
180.6 |
165.6 |
143.5 |
82.8 |
75 |
60 |
361.3 |
208.4 |
197.1 |
180.6 |
156.5 |
90.3 |
81 |
65 |
391.4 |
225.8 |
213.5 |
195.7 |
169.5 |
97.8 |
88 |
70 |
421.5 |
243.2 |
229.9 |
210.7 |
182.6 |
105.4 |
94 |
75 |
451.6 |
260.5 |
246.3 |
225.8 |
195.6 |
112.9 |
100 |
80 |
481.7 |
277.9 |
262.7 |
240.8 |
208.7 |
120.4 |
106 |
85 |
511.8 |
295.3 |
279.2 |
255.9 |
221.7 |
128.0 |
113 |
90 |
541.9 |
312.6 |
295.6 |
271.0 |
234.8 |
135.5 |
125 |
100 |
602.1 |
347.4 |
328.4 |
301.1 |
260.8 |
150.5 |
138 |
110 |
662.3 |
382.1 |
361.3 |
331.2 |
286.9 |
165.6 |
144 |
115 |
692.4 |
399.5 |
377.7 |
346.2 |
300.0 |
173.1 |
156 |
125 |
752.6 |
434.2 |
410.5 |
376.3 |
326.1 |
188.2 |
175 |
140 |
843.0 |
486.3 |
459.8 |
421.5 |
365.2 |
210.7 |
188 |
150 |
903.2 |
521.1 |
492.6 |
451.6 |
391.3 |
225.8 |
194 |
155 |
933.3 |
538.4 |
509.1 |
466.6 |
404.3 |
233.3 |
206 |
165 |
993.5 |
573.2 |
541.9 |
496.7 |
430.4 |
248.4 |
213 |
170 |
1023.6 |
590.5 |
558.3 |
511.8 |
443.4 |
255.9 |
219 |
175 |
1053.7 |
607.9 |
574.8 |
526.9 |
456.5 |
263.4 |
238 |
190 |
1144.0 |
660.0 |
624.0 |
572.0 |
495.6 |
286.0 |
250 |
200 |
1204.2 |
694.8 |
656.9 |
602.1 |
521.7 |
301.1 |
288 |
230 |
1384.9 |
799.0 |
755.4 |
692.4 |
599.9 |
346.2 |
313 |
250 |
1505.3 |
868.4 |
821.1 |
752.6 |
652.1 |
376.3 |
375 |
300 |
1806.4 |
1042.1 |
985.3 |
903.2 |
782.5 |
451.6 |
438 |
350 |
2107.4 |
1215.8 |
1149.5 |
1053.7 |
913.0 |
526.9 |
500 |
400 |
2408.5 |
1389.5 |
1313.7 |
1204.2 |
1043.4 |
602.1 |
563 |
450 |
2709.5 |
1563.2 |
1477.9 |
1354.8 |
1173.8 |
677.4 |
625 |
500 |
3010.6 |
1736.9 |
1642.1 |
1505.3 |
1304.2 |
752.6 |
750 |
600 |
3612.7 |
2084.3 |
1970.6 |
1806.4 |
1565.1 |
903.2 |
813 |
650 |
3913.8 |
2257.9 |
2134.8 |
1956.9 |
1695.5 |
978.4 |
938 |
750 |
4515.9 |
2605.3 |
2463.2 |
2257.9 |
1956.3 |
1129.0 |
1 PHASE AMPERES – 100% POWER FACTOR
(kW Times 1000) divided by Volts
kVA |
kW |
120 |
240 |
6 |
5 |
42 |
21 |
10 |
8 |
67 |
33 |
13 |
10 |
83 |
42 |
19 |
15 |
125 |
63 |
25 |
20 |
167 |
83 |
31 |
25 |
208 |
104 |
34 |
27 |
225 |
113 |
38 |
30 |
250 |
125 |
44 |
35 |
292 |
146 |
50 |
40 |
333 |
167 |
56 |
45 |
375 |
188 |
63 |
50 |
417 |
208 |
75 |
60 |
500 |
250 |
81 |
65 |
542 |
271 |
94 |
75 |
625 |
313 |
100 |
80 |
667 |
333 |
125 |
100 |
833 |
417 |
156 |
125 |
1042 |
521 |
188 |
150 |
1250 |
625 |
219 |
175 |
1458 |
729 |
250 |
200 |
1667 |
833 |
281 |
225 |
1875 |
938 |
288 |
230 |
1917 |
958 |
325 |
260 |
2167 |
1083 |
344 |
275 |
2292 |
1146 |
375 |
300 |
2500 |
1250 |
438 |
350 |
2917 |
1458 |
500 |
400 |
3333 |
1667 |
531 |
425 |
3542 |
1771 |
563 |
450 |
3750 |
1875 |
625 |
500 |
4167 |
2083 |
AMP
CONVERSIONS:
For kW, take WATTS and divide by 1000
POWER (WATTS) = VOLTS times AMPERES
AMPERES = POWER (WATTS) divided by VOLTS
VOLTS = POWER (WATTS) divided by AMPS
Did you know that US POWER & ENVIRONMENT is a turnkey Power Solutions Specialist offering complete turnkey standby power packages up to 45mW? We specialize in 100kW to 3 Mega Watt applications for industrial customers seeking heavy duty industrial standby generators for standby or continuous use. We can provide you with diesel, natural gas or propane powered units. We offer only top quality products that are priced at or below our competition who offer lesser brands with higher hours!